No delay is desired. Enter 0.00 for both.
Switching (section 4.2.4.4.3)
5.2.3.17. On / Off Delay (section 4.2.4.2.2)
5.2.3.18. Output
Relay 1 is being used as failsafe for speeds in excess of 440 rpm.
Select DA (de-energize above)
Enter 4.400e+2 for the Alarm setpoint.
Enter 3.500e+2 for the Safe setpoint.
Relay Output 2 Setup(Failsafe Underspeed alarm)
Navigate to Digital Output 2 setup. Make all constants the same except for Output
switching.
5.2.3.19. Output Switching (section 4.2.4.4.4)
Relay 2 is being used as failsafe for speeds below 270 rpm.
Select DB (de-energize below)
for the Alarm setpoint Enter +2.700e+2
Enter 3.500e+2 for the Safe setpoint.
Analog Output Setup
Navigate to the Analog output section. 4 to 20 mA will be used. 20mA
speed, 4mA will be for min speed.
the speed range to monitor. In
200 rpm)
will be the max
5.2.3.20. Source (section 4.2.5.1.1)
Set source to Input A.
5.2.3.21. Range (section 4.2.5.1.2)
Set range to 4 to 20 mA.
5.2.3.22. Min / Max Value (section 4.2.5.1.3)
Set the maximum and minimum values of
this case speed beyond the failsafe range will be included
Min Value = +2.000e+2 (
Max Value = +5.000e+2 (500 rpm)